The DC-UPS with Ethernet, such as the CBI60W and CBI600W series from Adelsystem, can switch the output that powers radios, routers and switches off and on from a remote location. With the watchdog function, the DC-UPS pings a configured IP address and, if no reply arrives, runs a controlled power cycle by itself. This reduces site visits for simple restarts.
A DC-UPS is a DIN rail module that combines an industrial power supply, a battery charger and battery monitoring, and keeps the connected equipment powered by the battery when the mains fails. In an Ethernet DC-UPS the interface also allows remote access to its functions, including switching the LOAD output on and off.
In the Adelsystem range, the CBI60W and CBI600W series have built-in Ethernet with an internal web server, Modbus TCP/IP, SNMPv3 and HTTPS. The models are CBI6012A (12 V 5 A), CBI6024A (24 V 2.5 A), CBI6048A (48 V 1.25 A), CBI60024A (24 V 25 A) and CBI60048A (48 V 12.5 A).
|
Term |
Meaning |
|---|---|
|
ISP / WISP |
Internet service provider / wireless internet service provider: networks made of distributed sites such as towers, rooftops and cabinets. |
|
NOC |
Network operations center: the control center that supervises the network. |
|
LOAD output |
The DC output of the DC-UPS that powers the connected equipment (radio, router, switch, gateway). |
|
Power cycle |
Switching the LOAD output off for a set time and then on again, so that the equipment fully restarts. |
|
Watchdog |
A function that periodically checks the reachability of an IP target and, if the expected replies are missing, runs a controlled power cycle. |
When network equipment is still powered but no longer responds, the LOAD output can be switched off and restored without going to the site. The DC-UPS therefore replaces an external IP relay.
The watchdog extends the remote power cycle by automating fault detection.
The DC-UPS periodically checks the reachability of a configured IP target.
If the expected replies are not received according to the configured logic, it executes a controlled power cycle of the LOAD output.
On radio towers, rooftops and other elevated installations, the remotely controlled LOAD output supports maintenance: the connected equipment stays de-energized during the intervention and power is restored only after personnel have left the elevated or restricted area.
The internal web server, Modbus TCP/IP, SNMPv3 and HTTPS interfaces give access to the DC-UPS parameters, so the unit can be integrated in SCADA platforms or IoT solutions. The operator can monitor AC input voltage; DC output voltage, current, power and status; battery voltage, current and internal resistance, and receive alarms on network, device and battery faults.
What is a watchdog on a DC-UPS?
It is a function that periodically pings a configured IP target and, if the expected replies are not received according to the configured retry and timeout logic, runs a controlled power cycle of the LOAD output.
Can a DC-UPS replace an external IP relay?
Yes. When the LOAD output of an Ethernet DC-UPS is controlled remotely, power management stays inside the same device used for backup, so an external IP relay is not needed.
How do I avoid a restart caused by a single lost packet?
Use retry and timeout logic: the power cycle starts only if the missing replies meet the configured criteria, not after one transient packet loss.
Why is a restart policy needed?
A restart policy prevents repeated cycles from masking a persistent network or hardware fault.
Does remote LOAD control replace lockout and isolation procedures?
No. Isolation, lockout and verification procedures required by the installation and by the applicable safety rules remain independent of the DC-UPS control function.
Which interfaces does the CBI60W series offer?
An internal web server, Modbus TCP/IP, SNMPv3 and HTTPS, for monitoring through SCADA platforms or IoT solutions.
Which equipment can be powered and restarted?
Radios, routers, switches, gateways and transmission equipment connected to the LOAD output, within the voltage and current of the chosen model.
For ISP and WISP sites, the difference is not the network topology but how the powered equipment is managed. An Ethernet DC-UPS adds three practical functions to power continuity: remote power cycling, automatic watchdog recovery and controlled LOAD management during maintenance at elevated or hard-to-reach sites. This makes the DC-UPS an active element of service restoration.